日本機械学会論文集 B編
Online ISSN : 1884-8346
Print ISSN : 0387-5016
水平ローフィン付管の縦列における凝縮液の流動特性
本田 博司野津 滋武田 泰仁
著者情報
ジャーナル フリー

1987 年 53 巻 488 号 p. 1320-1328

詳細
抄録
Experiments were performed to study the flow characteristics of condensate on a simulated bank of horizontal low finned tubes. Two or three tubes arranged in a vertical column were set in a stationary vapor. The top tube had a longitudinal slit at the upper end through which the test liquid was fed uniformly on the tube surface. Cooling water was passed through the lower tubes. The test fluids used were R-113, methanol and normal propanol. Four major flow modes: droplet, column, column-sheet and sheet, were observed as the liquid flow rate was increased. Experimental data on the number of instantaneous falling sites, the proportion of surface area covered with the falling liquid and the flooding angle below which the inter-fin sp. ace was flooded with condensate were obtained for a range of liquid flow rates. Theoretical considerations were given to the effect of liquid flow rate on the flow mode transition and on the measured quantities.
著者関連情報
© 社団法人日本機械学会