連結管を持つ二相熱サイフォンの熱輸送限界
加熱面温度変動と流動特性
井上 利明門出 政則朝倉 正樹
著者情報
ジャーナル フリー

2007 年 73 巻 726 号 p. 610-615

詳細
抄録

An experiment of heat transfer characteristics in a two-phase thermosyphon with an adiabatic connecting pipe of inner diameter Dp=2 to 8mm and of length L=250, 500 and 1000mm has been carried out at atmospheric pressure employing water as an operating substance. As the heat is loaded into the thermosyphon, the temperature of heated surface starts fluctuating at a heat flux at which unstable vapor-liquid counter current flow is generated in the connecting pipe. A feature of bubbles at the upper end of the connecting pipe was photographed when the temperature fluctuation starts. It was found that the heat flux at the onset of the temperature fluctuation is increase with an increase in Dp and then can be predicted well by the Wallis equation with Cw=0.7 for 5≤Dp≤8mm. Furthermore, we clarified that the cause of this fluctuation comes from the inlet effect of the connecting pipe using a bell mouth, which is placed to either bottom end or both ends of the connecting pipe.