Quarterly Report of RTRI
Online ISSN : 1880-1765
Print ISSN : 0033-9008
ISSN-L : 0033-9008
PAPERS
Development of a DC Feeding Bus Ground Fault Detection System for Railway Substations
Hiroaki MORIMOTOShin-ichi HASEToru AIHARA
著者情報
研究報告書・技術報告書 フリー

2005 年 46 巻 2 号 p. 103-109

詳細
抄録
High-voltage DC ground relays (64P) are commonly used at DC railway substations to detect DC feeding bus ground faults, which may cause fire or other serious damage. Therefore, 64P relays, which send a command to open all related circuit breakers, are very important devices. However, 64P relays sometimes disrupt railway traffic because they are occasionally activated by irrelevant faults, such as ground faults at external feeding lines or other substations. We are now developing a new method of detecting DC bus ground faults that can eliminate the influence of unrelated faults. This paper gives an outline of the new method and the results of basic investigation.
著者関連情報
© 2005 by Railway Technical Research Institute
前の記事 次の記事
feedback