E-8 煙突効果の抑制対策に関する研究 : 対策運転による差圧低減効果の測定
新村 浩一大森 一郎小林 浩次飯嶋 和明
著者情報
会議録・要旨集 フリー

詳細
抄録
This study aim is to examine the countermeasure of stack effect in super high-rise buildings at winter season. In this paper, two countermeasures were operated. First operation is for elevator shaft, cool flesh air is supplied from the lowest shaft by fan, and warm shaft air is exhausted from the top by fan. Second operation is for room in upper floor, surplus exhaust air is reduced by air-condition control, and pressure in elevator hall is added. Those operations effects were evaluated by measurement of pressure and temperature.