D-18 Study on Non-Condensing Air-Conditioning System for Next Generation (Part 11) : Study on the Applicability of Desiccant Air-Conditioning System Providing Humidification/Heating in Winter
Yaw-Shyan TSAYShinsuke KATORyozo OOKAMakoto KOGANEINorio SHODAKoichi KAWAMOTOKousaku NISHIDAWanghee CHO
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
A conventional desiccant air-conditioning system is almost considered providing only dehumidification and cooling usage in the past studies. However, the system can be used in reverse for humidification/heating to deal with the cold and dry climates, such as the winter period of Tokyo. In this paper, a desiccant air-conditioning system providing humidification and heating usage is proposed, and two kinds of desiccant materials of the proposed system are studied experimentally. In this system, vapor from the outdoor air is the moisture source, and the heating and humidification power is sufficient under the weather in early March in Chiba city. With different regeneration temperature and flow rate ratio between adsorption side and humidification side, heating and humidification power are possible to be controlled to fit the load of the buildings.
Content from these authors
© 2006 The Society of Heating,Air-Conditioning&Sanitary Engineers of Japan