Techinical Papers of Annual Meeting the Society of Heating,Air-conditioning and Sanitary Engineers of Japan
Online ISSN : 2424-2179
Print ISSN : 1880-3806
ISSN-L : 1880-3806
2006.1
Session ID : F-14
Conference information
F-14 Emission of Volatile Organic Compounds and Aldehydes from Floor Heating sysytem in Experimental Timber House
Minoru OKABEHaruki OSAWAYasuo KUWASAWA
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
Floor heating system is widly used in Japan. Japanese building code about indoor air quality was based on 28 degree temperature and 50% humidity in summer. Floor heating system have made of plywood, MDF and other woodbased material included folmaldehyde and when running floor heating in winter, temperature inside the floor heating system become above 28 degree. When floor heating system running in winter, it is required to measure the indoor air quality in the full size house. Hot-water system and electric heater system was constructed for interior finish of the house and indoor chemical substance concentration was measured. Folmaldehyde concentration showed below the 100ug/m^3 for running floor heating system in winter.
Content from these authors
© 2006 The Society of Heating,Air-Conditioning&Sanitary Engineers of Japan