Techinical Papers of Annual Meeting the Society of Heating,Air-conditioning and Sanitary Engineers of Japan
Online ISSN : 2424-2179
Print ISSN : 1880-3806
ISSN-L : 1880-3806
2006.2
Session ID : E-38
Conference information
E-38 Research on the Ceiling Radiant Air Conditioning System in a Library : (Part2) Winter Survey Result (Examination of Operation Parameter)
Hidemi YAMAOSatoshi TERASHIMARyouichi KUWAHARANorio KITOMasayasu OKADO
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
We measured again by the lower supply water temperature to the radiant panel based on the pre- report result. We verified the thermal comfort of stable operation, the warming up performance at the day next closure day and the amount of consumption energies. It became clear that the optimal temperature to the panel at heating term was 26℃ for this institution.
Content from these authors
© 2006 The Society of Heating,Air-Conditioning&Sanitary Engineers of Japan
Previous article Next article