G-37 空気清浄ユニット付き換気システムのホルムアルデヒド除去性能の実態と試験法の提案に関する研究
野傭 淳夫佐々木 俊成田 泰章
著者情報
会議録・要旨集 フリー

詳細
抄録
In order to evaluate the chemical substance removal performance of a ventilation system correctly, it is important to establish a performance evaluation method. The purpose of the present study is to evaluate the removal performance of chemical substances on a ventilation system using two evaluation methods and to compare them. We experimentaly tested the ventilation system with air cleaning units, it turned out that the clean air delivery rates (CADR) of formaldehyde ranged from 29.0 to 31.4 [m^3/h] during initial operations. The correspondence rates between CADR derived from a one-pass method and that derived from a constant-emission method were 92.4 percent for formaldehyde.