H-24 Stocktaking on the cooling, heating and hot-water supply load characteristics of hospitals
Takumi OHASHIKenji WATANABEHiroaki TANAKA
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
In this report, the stocktaking was carried out to investigate the load characteristic of cooling, heating and hot-water supply on the recent general hospitals. The results are as follows; 1) The monthly cooling load rates in the intermediate season were higher than that of the exiting SHASE data. 2) The hourly cooling load rates in the nighttime were higher than that of the exiting data. 3) The annual integrated hot-water supply load rates were lower about 1/3 than that of the exiting data. 4) The cooling and heating load in the daytime on weekday were higher than from that on weekend.