C-46 非結露型次世代空調システムに関する研究(その12) : 夏季通期を通しての試算と評価
川本 光一加藤 信介小金井 真大岡 龍三生田 紀夫蔡 耀賢西田 耕作趙 旺煕
著者情報
会議録・要旨集 フリー

詳細
抄録
The purpose of this study is to realize a non-condensing environment by developing a new type of desiccant air-conditioning system with higher energy efficiency. In this paper, the overall energy efficiency and IAQ of new type of desiccant outdoor air-conditioning systems which are combined with CO_2 heat pump are compared with those of the conventional outdoor air-conditioning systems, by simulated calculation at typical hotel rooms over summer period.The results show that the system COP of the proposed systems is considerably higher than those of the conventional outdoor air-conditioning systems, although non-condensing environment and higher level of IAQ is achieved.