I-64 集合住宅の換気システムに関する研究 : (第1報)現場における換気口通気性能の経時変化の測定
木村 洋西村 欣英
著者情報
会議録・要旨集 フリー

詳細
抄録
Indoor negative pressure by simultaneous use of exhaust fans causes such problems as increase of power needed for opening entrance door. In order to evaluate air-flow rate deterioration of ventilating openings in continuous ventilation, field measurement was conducted in apartment buildings for three months. The result showed that air-flow rate of ventilation filters decreased 3-8% during the period. Also, their dust removal performance remained throughout the period, and its air-flow rate was estimated to decrease around 5-15% in half year.