主催: 公益社団法人 空気調和・衛生工学会
In this part report, heat recovery unit (modular water to water heat pump with scroll compressor controlled by variable-frequency-drive) is investigated and formulated as additional equipment. And dynamic performance model of central plant equipment using the single time constant regressive approximation is proposed. Sequential order and the time steps of central plant components is used to represent single time constant regressive approximation.