配電系力率測定用電圧検出センサの実用化に関する研究
古川 達也嶋田 英樹相知 政司
著者情報
ジャーナル フリー

1995 年 31 巻 11 号 p. 1810-1816

詳細
抄録
In general, since voltage in transmission lines is so high that the wave form need to be measured with static induction type of voltage sensor, which comprises a pair of electrodes, there should exist a problem on the discrepancy between the actual voltage wave form and the measured one in three phase power distribution systems owing to the mutual electric induction between each other phase.
We shall present the numerical electric field analysis of the sensors in such a power distribution system using two dimension finite element method taking account of the unknown equi-potentials and the complex permittivity to clarify the difference between the impressed voltage wave form across the electrodes of such a sensor and the actual voltage wave form.