NIPPON SUISAN GAKKAISHI
Online ISSN : 1349-998X
Print ISSN : 0021-5392
ISSN-L : 0021-5392
Heat Admitted into a Cold Storage Room by its Door-opening
Tamotu AMASAKIAkasi HASEBE
Author information
JOURNAL FREE ACCESS

1935 Volume 4 Issue 3 Pages 198-202

Details
Abstract

From his experimental results, H. S. WHITESEL has given an empirical formula to estimate the heat load of the door-opening for a household refrigerator cabinet. To ascertain that his formula is equally applicable or not to a cold storage room of a larger size, we had made some experiments with a cold storage room, which has a preliminary chamber 168 ft3 and a cold storage chamber 216 ft3 in the internal volume respectively.
The results of our experiments have also shown that the values calculated from WHITESEL'S formula are nearly equal to the measured values in the case, where the door-opening takes place between the open room air and the preliminary chamber; but for the case, where the door-opening takes place between the preliminary and the cold starage chambers, the volume of the latter being larger than that of the former, his formula must be modified.

Content from these authors
© The Japanese Society of Fisheries Science