自然通風型低レベル放射性廃棄物貯蔵施設の熱流動特性評価
吉井 敏浩岩城 智香子小山 友紀碓井 伸彦渡辺 久夫池田 達實池田 浩正木 嘉一
著者情報
ジャーナル フリー

2012 年 11 巻 1 号 p. 91-100

詳細
抄録
  It is necessary to design a low level radioactive waste storage system so that the decay heat of radioactive waste does not breach the structural safety limit. Currently, this waste storage system is designed as a natural cooling system, which continuously cools the radioactive waste without an active device. It consists simply of a storage pit for radioactive waste and air inlet and outlet ducts. The radioactive waste is cooled by natural convective air flow, which is generated by the buoyancy of heated air due to the decay heat of radioactive waste. It is important to clarify the flow characteristics in the systems in order to evaluate the cooling performance. The air mass flow rate through the system is determined by the balance between the natural convective flow force and pressure loss within the system. Therefore, the pressure drop and flow pattern in the waste storage pit are important flow characteristics. In this study, the pressure drop and air temperature distribution, greatly influenced by the flow pattern in the pit, were measured using a 1/5 scale model and compared with the results obtained from CFD. Flow network analysis, which is a simple model that simulates the flow by nodes and junctions, was conducted and its validity was confirmed by experimental results and CFD.