事務所ビルにおける自然換気時の室内空気質環境および省エネルギー性に関する研究
庄司 研桑原 三香大黒 雅之鹿毛 比奈子大野 茂深尾 仁田村 明弘
著者情報
ジャーナル フリー

2012 年 77 巻 679 号 p. 729-735

詳細
抄録

In this study, considering the outdoor air quality when natural ventilation estimated that high concentrations due to the closure of the opening, that aims to determine the impact on the reduction of cooling load.
We calculate the airflow and contaminant concentration distribution with CFD analysis in the three models, the results are reflected, thermal and airflow network analysis was performed by annual meteorological data.
One result of analysis that openings were restricted to prevent the flow of outdoor pollutants, total natural ventilation time was about 50% shorter. And the cooling load was decreased by 10%.