東京都内の機械換気設備を有する小学校普通教室における新型コロナウイルス感染症対策としての環境調節が換気量および温熱環境へ及ぼした影響
合原 妙美岩下 剛田辺 新一
著者情報
ジャーナル フリー

2023 年 88 巻 806 号 p. 352-363

詳細
抄録

Air temperature and CO2 concentration were measured in classrooms with ventilation system from April 2018 through March 2022. It is assumed that, under the COVID-19 circumstances, windows of the classrooms, where ventilation system was working, were basically kept open throughout a year. The average air temperature at foot level was 11°C during winter period because of cold outdoor air infiltration. The estimated ventilation rate tended to decrease during winter period. However, the estimated ventilation rate per person more than 30 m3/h was obtained in case of half number of pupils in the classroom with Hybrid-Flexible lesson for the whole day.