日本建築学会構造系論文集
Online ISSN : 1881-8153
Print ISSN : 1340-4202
ISSN-L : 1340-4202
火災区画内発熱量に係わる燃料の違い : 火災区画内の発熱量の予測 その2
成瀬 友宏菅原 進一
著者情報
ジャーナル フリー

1999 年 64 巻 521 号 p. 157-161

詳細
抄録

Following the part 1, this paper discusses about heat release, combustion efficiency, mole weight and density of burned gas of methanol, methane, propane and Douglas Fir in fire compartment and about the difference among them. Consequently on the assumption of previous and this paper, heat release per gram of oxygen in air consumed and combustion efficiency of methanol and Douglas Fir decrease, as equivalence ratio φ (the fuel-air mass ratio normalized by the stoichiometric fuel-air mass ratio) increases, because of the consumption of heat in their latent heat of non-reacted fuel. The combustion efficiency of methane shows relatively good relation to the previous work.