中廊下型共同住宅の火災事例調査 : 火災・煙による被害範囲と建築側条件・防災設備の状況(防火)
長谷見 雄二古川 容子大山 有紀子徳永 未来柿木 英治
著者情報
ジャーナル フリー

2004 年 10 巻 19 号 p. 163-168

詳細
抄録
On-site investigation and interviews to residents are conducted on a fire in an apartment building which resulted in the notable fire and smoke damage throughout the building not lower than the floor of the fire initiation. The extensive smoke damage is attributed to the failure of the closure of the fire doors of the staircase, probably due to the aging of either the fire detecting fuses or the automatic door closers. Unawareness of the gang-ways by the evacuees resulted in the notable difficulties in the evacuation from numbers of the dwelling units.