日本建築学会技術報告集
Online ISSN : 1881-8188
Print ISSN : 1341-9463
ISSN-L : 1341-9463
環境工学
新築保育施設における空気質改善方法
TVOC濃度変化を指標とした室内空気質評価
野口 美由貴水越 厚史柳沢 幸雄
著者情報
ジャーナル フリー

2011 年 17 巻 36 号 p. 577-582

詳細
抄録

Evaluation of air quality by concentration of just only target compounds has the possibility of a lot of trouble. In this study, we evaluated the air quality of new nursery room. As a result, the TVOC concentrations greatly exceeded the indoor target value (400 μg/m3). Moreover, we verified various ventilation methods such as continuous running of kitchen fan, securing of ventilation routes and introduction of additional ventilating fan, and the concentration drastically decreased to one-tenth compared with opening status after 3 months. In addition, ventilation rates estimated by TVOC concentration change of PID monitor increased.

著者関連情報
© 2011 日本建築学会
前の記事 次の記事
feedback
Top