A design method for distributed battery storage capacity has been developed for evaluating battery storage advantage on demand-supply imbalance control in distribution systems with which large-scale home photovoltaic powers connected. The proposed method is based on a linear storage capacity minimization model with design basis demand load and photovoltaic output time series subjective to battery management constraints. The design method has been experimentally applied to a sample distribution system with substation storage and terminal area storage. From the numerical results, the developed method successfully clarifies the charge-discharge control and stored power variation, satisfies peak cut requirement, and pinpoints the minimum distributed storage capacity.