Control Performance of Single-Phase STATCOM and BTB by Three-Level Inverters
Shinzo TamaiHirofumi Akagi
Author information
JOURNAL FREE ACCESS

2005 Volume 125 Issue 3 Pages 221-228

Details
Abstract
The so-called three level inverters have been widely used for industry applications because of high-voltage output ability and low harmonic contents. These applications are mainly suitable for ac motor drives. Nowadays, attention has been paid to larger-capacity inverters applicable to power system control. This paper describes their applications to power systems. First, harmonic analysis of a three-level inverter is achieved under the condition that its two dc capacitor voltages are unbalanced. Second, a control method for balancing the two dc capacitor voltages is described. Finally, applications of single-phase three-level inverters to STATCOM and BTB are introduced. Their control performance is confirmed by computer simulation.