IEEJ Transactions on Industry Applications
Online ISSN : 1348-8163
Print ISSN : 0913-6339
ISSN-L : 0913-6339
Paper
Development of New Type Gap Arrester for Earth Fault Protection in AC Feeding System
Kohji AjikiHiroaki MorimotoYasuzi HisamizuNobuo KinoshitaWataru TakaiRyogo Sato
Author information
JOURNAL FREE ACCESS

2006 Volume 126 Issue 11 Pages 1493-1499

Details
Abstract
A gap arrester is being used for ground fault protection in AC Feeding System. However there are faults in which a conventional gap arrester burns down in a normal state of circuit. We investigated the cause of the fault in which a gap arrester burns. Then, it was found out that the cause of the fault was the discharge of AC current from the surge voltage. Therefore, we developed a new type gap arrester which does not burn down. The new type gap arrester is composed of a discharge tube and a zinc oxide element which are connected in series. Unnecessary AC current discharge is prevented by this structure. The new type gap arrester is actually used at the railroad track.
Content from these authors
© 2006 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback
Top