電気学会論文誌B(電力・エネルギー部門誌)
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
論文
トラック型ZCTの巻線方法改善による残留電流低減の検討
岩崎 文雄伊部 正之二野瓶 耕一郎岡村 清一朗
著者情報
ジャーナル フリー

2006 年 126 巻 1 号 p. 51-58

詳細
抄録
ZCT (Zero-phase-sequence Current Transformer) is used widely for the detection of the ground fault current in low or high voltage distribution power line. Especially, the use of pole air switches equipped with ZCT is increasing to prevent the extended accident caused by the ground fault. The accurate detection of low level ground fault is needed from the view of early stage discovery. The internal residual current of ZCT must be small as possible for the detection of low level ground fault. Generally, the magnetic shield around the core of ZCT is used to reduce the internal residual current. Also, the core material and shield effect is related to the reduction of the internal residual current. In this paper, the reducing method of the internal residual current is proposed by using new winding method of the core. In new winding method, the secondary and tertiary windings are provided, and each winding is divided into two or three sections with parallel connection. The leakage magnetic flux caused by the primary current is changed to the cross current in parallel winding. This cross current is used to offset the leakage magnetic flux caused by the primary current. It is observed by the examination that the cross current is effective to reduce the internal residual current without influence to the zero phase current detection.
著者関連情報
© 電気学会 2006
前の記事 次の記事
feedback
Top