PV出力に応じた無効電力制御によるSVC容量低減効果と配電線路損失への影響評価
八太 啓行
著者情報
ジャーナル フリー

2015 年 135 巻 2 号 p. 106-110

詳細
抄録
When a large number of photovoltaic (PV) power generations are installed in the distribution system, it is expected that distribution line voltage will fluctuate by the PV output. Then, the large capacity of SVC may be required because the distribution line voltage cannot be controlled by only SVR operation. In this paper, a reactive power control method in proportion to the PV output change is proposed to reduce the capacity of SVC by complementing SVR operation. By the simulation analyses, it was shown that the capacity of the SVC was reduced by the proposed reactive power control. In addition the distribution line loss of the proposed method was smaller than that of the constant power factor control.