2016 年 136 巻 11 号 p. 817-823
Real-time pricing will be one of the realization methods of demand response scheme for the future smart grid. Assuming an advanced building energy management system for multi-type packaged air-conditioning facilities in commercial buildings, simulated annealing optimization that minimizes an evaluation function consisting of power cost and comfort degradation terms was studied. Experiments using an actual office building showed the result of reducing power consumption by 39% while keeping the room temperature degradation by only 0.16 degrees on average for an example case of ten-minute interval real-time pricing.