太陽光発電の大量連系を考慮した業務用空調機制御による系統調整力の経済性評価
髙木 健太郎浅野 浩志坂東 茂
著者情報
ジャーナル フリー

2017 年 137 巻 10 号 p. 678-686

詳細
抄録

High penetration of intermittent renewable energy such as photovoltaic (PV) and wind power could cause shortage of power system flexibility. Demand response is expected to help supply ancillary service instead of the conventional power plant. Commercial air conditioners are a promising responsive load for demand response because they account for a large proportion of power consumption in the power system. We calculate a system operation cost and hourly operation pattern of each power plant by using the optimal power generation model considering flexibility supply from controlling commercial air conditioner. We obtained the following results as an effect of commercial air conditioner control. (1) The power generation of oil-fired power plants decreases at peak time and annual fuel cost of oil-fired plant is reduced by approximately 30% at most in Kanto area. (2) The percentage of rated operation mode of LNG combined cycle plants increases. (3) Curtailed energy rate of PV decreases because a power storage amount by pumped hydro power generation increases. (4) Required battery capacity to reduce PV curtailed amount decreased by combining battery energy storage system in case of high penetration of PV.