Equal area criterion is frequently used as a means to assess transient stability. The method can be hardly applied to observed data because the method is based on rotor angles which need to be measured with specially deployed sensors. This paper presents the equal area criterion using generator terminal voltages instead of the rotor angles. It is easy to measure the voltages, thus the novel method would be more acceptable to industry.