Journal of Asian Architecture and Building Engineering
Online ISSN : 1347-2852
Print ISSN : 1346-7581
Environmental Engineering
Evaluation of the Energy and Environmental Performance by Introducing a District Energy System
----Summer Field Study at Kitakyushu Science and Research Park
Weijun GaoNan ZhouBill BattyMasaru NishidaNoriyasu SagaraYuji Ryu
著者情報
ジャーナル フリー

2004 年 3 巻 2 号 p. 291-296

詳細
抄録
In Kitakyushu Science and Research Park, a new district energy system has been introduced. In this study, we chose this system as a case study and have carried out an analysis on the efficiency of the power generation and heat release utilization of the fuel cell and gas engine in summer by using recorded data.
The results can be summarized as follows; 1) Although the power generation efficiencies of the gas engine and fuel cell are slightly lower than the standard designated value, they are almost constant throughout the period of study. 2) The collected heat energy is lower than the designated value. The heat release utilization, which is used for cooling and hot water, is lower than expected. Considering the efficient use of energy for such systems, it is important to have a good use of heat release when we introduce a district energy system. 3) The discarded heat energy of the system is very big in this investigation when evaluating the system as a whole. It is fundamental to the future of energy conservation to use primary energy more efficiently.
著者関連情報

この記事は最新の被引用情報を取得できません。

© 2004 Architectural Institute of Japan