防音聴力検査室の環境 (換気, 特に冷房・除湿について)
西岡 敏之圓山 幸子島野 藤祐向井 貞三
著者情報
ジャーナル フリー

1967 年 13 巻 1 号 p. 49-56

詳細
抄録
The design of a sound-proofed room has laid emphasis on the protection from outside noise and the sound-damping of inside noise, while ventilation and airconditioning have not been put into so much consideration.
In Yao Municipal Hospital the author studied the temperature and humidity of the sound-proofed room under air-conditioning in summer.
The following facts were obtained:
1) The noise of the air-conditioning machine was pardonably muffled by the silencer, which did not damage sound proofing and ventilation.
2) By ventilation the air humidity was reducced to 70%.
3) In case of the sound-proofed box in the sound-proofed room, the inside temperature was reduced to 0.03 to 0.09 degree per minute by keeping the door open.