TCSCの電圧及び電流基準同期系の特徴比較
松木 純也長谷川 慎治安陪 稔
著者情報
ジャーナル フリー

1997 年 23 巻 2 号 p. 9-16

詳細
抄録
This paper presents the results of experimental study on the effects of synchronization systems for a thyristor controlled series capacitor (TCSC). A comparison has been made between two different synchronization schemes: synchronization with respect to zeros of TCSC capacitor voltage and synchronization with respect to zeros of line current. No such comprehensive investigation has been reported in the literature yet. A laboratory-scale TCSC has been designed, produced and installed in a laboratory power system at Kyoto University. Effects of the two synchronization systems on the performances of TCSC have been investigated on the experimental system. Steady-state impedance characteristics, dynamic response, and instability of TCSC in a variety of operating conditions have been compared. Both advantages and disadvantages of the two synchronization systems have been clarified.