吸収材を用いた熱駆動型冷凍機の反応評価
江崎 丈裕小林 敬幸
著者情報
会議録・要旨集 フリー

詳細
抄録

Here, we propose a chemical heat pump chiller with a SrBr2 hydration reaction system for utilization of waste heat. The SrBr2 hydration reaction could recover waste heat in low temperatures ranging from 373 to 353K, and the system showed good potential in terms of the high cooling thermal-storage density. Previous studies have given little information on the reaction characteristics of the SrBr2 hydration reaction. In this paper, we developed a measuring method for the hydration reaction equilibrium and reaction rate based on the volumetric method. We analyzed the hydration reaction rate with an unreacted-core shell model. In the experiments, the SrBr2 equilibrium temperature observed was equal to the theoretical equilibrium temperature obtained from thermodynamic databases. In addition, the hysteresis gap between the hydration and dehydration values was 2.0 K. Thus, the hysteresis effect was negligible for the chemical heat pump cooling operation. The reaction fraction of the SrBr2 hydration reached 0.7 within 20 s. By analyzing the hydration reaction rate with the unreacted-core shell model, the activation energy value was calculated to be 56.6 (kJ/mol). The calculation results showed good agreement with those of the experiment as the reaction fraction reached 0.7.