動力・エネルギー技術の最前線講演論文集 : シンポジウム
Online ISSN : 2424-2950
2017.22
セッションID: B134
会議情報

流下液膜を用いた蒸気と不凝縮ガスの冷却について
*真下 景吉村 浩一山下 勝也坂上 英一古屋 修
著者情報
会議録・要旨集 フリー

詳細
抄録

Since non-condensable gas is contained in the steam at geothermal power plant, it is required for the purpose of simplifying a gas discharge system for plant efficiency improvement that emission gas should be made to fully cool and a volume flow should be made small. It is common to adopt how to cool the gas by direct contact for geothermal energy. We researched the cooling capability by the direct contact with the falling liquid film using structured packing. Experimental apparatus (Figure1) mainly consists of an evaporator, a cooling unit, and a vacuum pump. In the cooling section at the test equipment, Mixed gas(steam and air) and cooling water were floated by opposed flow : Mixed gas flows upward, and steam flows downward. Our conclusion in the experiment is that the cooling capability of falling liquid film has sufficient capability to cool mixed gas with high non-condensable gas density to cooling water temperture.

著者関連情報
© 2017 一般社団法人 日本機械学会