A108 管内流動抵抗低減剤の評価 : 空調用熱交換器におけるDR効果と熱交換特性(オーガナイズドセッション1 : 機能性流体の熱伝達)
井口 泰男工藤 敏洋
著者情報
会議録・要旨集 フリー

詳細
抄録
It is known that drag reducing additive reduce turburent friction drag and heat transfer in tube flow simultaneously. Then, the reducing chracteristics of drag and heat transfer of surfactant(Ethoquard 0/12) solution flow in the finned-tube heat exchanger (pipe di. 9.3mm) for air-conditioning were measured in the experimental room controlled temperature and humidity, before field test. The following results were obtained. (1)As cooling, it was not showed the reducing chracteristics of drag and heat transfer. Conversely, it was showed the increasing chracteristics of drag. (2)As heating, the reducing chracteristics of drag and heat transfer depended on the type of heat exchanger.