空気調和・衛生工学会大会 学術講演論文集
Online ISSN : 2424-2179
Print ISSN : 1880-3806
ISSN-L : 1880-3806
平成19年
セッションID: C-48
会議情報
C-48 吸収液除湿式空気調和方式によるクリーンルーム空調エネルギー削減の研究開発 : (第1報) 研究概要と基礎実験
永坂 茂之松本 尚史佐々木 央植村 聡菅原 一彰大見 忠弘白井 泰雪
著者情報
会議録・要旨集 フリー

詳細
抄録

This Study features research and development into a novel air conditioning system to halve the energy used for air conditioning, which represents 40% of the total energy consumption in clean rooms. The main target involves developing new outdoor air treatment equipment requiring no refrigerators. The operational conditions of the liquid desiccant system were determined by experiments. The method of membrane distillation under vacuum was selected from the several means of regeneration available, excluding evaporation by heating. Energy saving features for vacuum systems can be planned if our semiconductor manufacturing technology and newly developed pumps are installed.

著者関連情報
© 2007 公益社団法人 空気調和・衛生工学会