G-24 事務所ビルにおける浮遊粒子状物質の粒径分布とエアフィルタによる除去効果
鍵 直樹柳 宇池田 耕一西村 直也齋藤 秀樹齋藤 敬子鎌倉 良太
著者情報
会議録・要旨集 フリー

詳細
抄録
This study aimed at investigating particulate matter (PM) in office buildings and collection efficiency of ultra fine particles by air filter media. Particle matters (PM) in 15 off ce buildings were measured as mass concentration with a low-volume air sampler and a beta ray attenuation method, and as count concentration with a wide-range particle spectrometer (WPS). The correlation between the mass concentration of PM and PM2.5 and concentration calculated with WPS were investigated. The fine particles around 100nm diameter were not collected onto the air filter media, and the air from diffuser in the room could evacuate ultra fine particle instead of supplying the air through the air filter.