空気調和・衛生工学会大会 学術講演論文集
Online ISSN : 2424-2179
Print ISSN : 1880-3806
ISSN-L : 1880-3806
平成19年
セッションID: B-43
会議情報
B-43 蓄熱式空調方式における熱搬送システムの動力削減に関する研究 : (その6) バッフル板の改良と貯氷タンクからの氷水取り出し特性
野笹 励一神谷 是行
著者情報
会議録・要旨集 フリー

詳細
抄録
Three leaves type baffle plate attached at the inlet of the sub-chamber of the temporary ice storage tank and new method of drawing ice/water mixture from the temporary ice storage tank by shaving ice mass were proposed and their performances were examined in this paper. Under examined conditions, proposed baffle plate prevents inflow of ice to the sub-chamber of the temporary ice storage tank and does not interfere drawing ice from the temporary ice storage tank. IPF of drawing ice /water mixture increased with the increase of rotational speed of shaving board and decrease drastically with the decrease of ice mass remained in the temporary ice storage tank. Furthermore power of motor driving shaving board is larger than that rotating ice mass of the previous method, but total power to draw ice/water mixture consumed in the proposed method is less than that in the previous method.
著者関連情報
© 2007 公益社団法人 空気調和・衛生工学会