抄録
We assumed the work area and measured the current of air velocity in unidirectional airflow from ceiling. It is preferable to form the unidirectional airflow so that pollution should not diffuse. The criterion of the mean velocity of above the floor level 900mm and 1500mm is 0.25m/s or more. We obtained the result of the relation between the angle and the distance at the ciling diffuser.