The Transactions of the Institute of Electrical Installation Engineers of Japan
Online ISSN : 2433-4472
ISSN-L : 2433-4472
Volume 41, Issue 8
Displaying 1-1 of 1 articles from this issue
  • Tatsuya Mutakamihigashi
    2021Volume 41Issue 8 Pages 53-60
    Published: 2021
    Released on J-STAGE: September 10, 2021
    RESEARCH REPORT / TECHNICAL REPORT FREE ACCESS
    An epoxy molded equipment is installed in various high voltage circuit. It is because epoxy molded equipment is nonflammable and can be made in small. And more, it has been thought that an epoxy molded equipment is not need to maintenance. However by over time, when cracks are formed in the epoxy resin, a partial discharge occurs at the position. As a result, dielectric breakdown is caused by continuous partial discharge occurring. So partial discharge diagnosis method has been hoped to be developed. Therefore we performed a partial discharge characteristics test for epoxy resin, then we could develop a diagnosis method detecting electromagnetic waves associated with a partial discharge. A frequency analysis is applied to the diagnosis method, the method can identify a state and a position of partial discharge. It is considered that our method is useful because it can be applied to a dielectric degradation diagnosis for an epoxy molded equipment in service.
    Download PDF (3224K)
feedback
Top