日本建築学会計画系論文集
Online ISSN : 1881-8161
Print ISSN : 1340-4210
ISSN-L : 1340-4210
高性能繊維層フィルターにおけるリークの特性
西村 直也藤井 修二湯浅 和博
著者情報
ジャーナル フリー

1999 年 64 巻 515 号 p. 83-88

詳細
抄録

Air filter leakage is one of the most important control point for verification and qualification of cleanliness of cleanrooms. In this paper, a model that expresses the number of penetrated particles through high-efficiency fibrous air filter with pin hole is proposed, by using 3 dimensionless parameters for the fundamental study of establishing filter leakage testing method. Leak rate and limitation of judgment caused by the difficulty of identifying the leakage particles from all the particles are calculated. The result of the calculation is that the face velocity have a great influence on the leak rate and limitation of judgment.

著者関連情報
© 1999 日本建築学会
前の記事 次の記事
feedback
Top