集合住宅の第1種集中換気システムの風量低下要因に関する調査(環境工学)
村田 さやか高倉 政寛鈴木 大隆福島 明片岡 尚大西 茂樹
著者情報
ジャーナル フリー

2005 年 11 巻 22 号 p. 307-310

詳細
抄録
In this paper, the causes of insufficient air volume of a heat- exchanging-type mechanical ventilation system installed apartment were investigated. The results are as follows: 1) Pressure-drop coefficients of the grills were excessive. 2) The blades of the exhaust fan were covered with dust and the power of that fan was less than cleaned one. 3) Pressure-drop coefficients of the filters stuffed with dust without maintenance were also excessive.