断面が急変するピロティ柱梁接合部における柱主筋の定着性状
花井 伸明後藤 康明市之瀬 敏勝
著者情報
ジャーナル フリー

2009 年 15 巻 29 号 p. 143-146

詳細
抄録
Experiments were carried out to examine the anchorage of column rebars for RC buildings with pilotis floor where the column depth greatly reduces. All the specimens failed in raking-out before the flexural yielding. It is important to avoid greatly reducing the column depth. When it is unavoidable to reduce the column depth; to transfer the column stresses to other members surely, note that: (1) the depth of beam over the pilotis floor should be as large as the column rebars are developable, (2) the beam bottom should be reinforced longitudinally enough.