日本建築学会技術報告集
Online ISSN : 1881-8188
Print ISSN : 1341-9463
ISSN-L : 1341-9463
環境工学
事務所ビルにおける室内浮遊粒子の特性とPM2.5濃度の実態調査
鍵 直樹西村 直也柳 宇
著者情報
ジャーナル フリー

2012 年 18 巻 39 号 p. 613-616

詳細
抄録
Characterization and emission of indoor sub-micron aerosols have been of great interest. This study aimed at investigating for characteristics of particle concentrations for size distribution in office buildings. The number of size distributions, PM2.5 and SPM (less than 10 μm) mass concentrations were measured in 15 large office buildings that were over 3,000m2 of total floor areas and had central HVAC systems.
As a result, the mass concentration shows a bimodal distribution at around 0.2-0.3 μm and 4 μm, while the number concentration has a smaller peak at 0.02 to 0.05 μm. The results of other buildings have the same trend of particle size-distributions.
Every mass concentration was relatively low, except for the building, which had smoking area inside. PM2.5 ratios (PM2.5/SPM conc.) were around 0.8, and therefore SPM forms the greater part of PM2.5. The peak of mass concentration distribution around 0.2 μm has a great effect on PM2.5 concentrations. The sub-micron particles might penetrate through filter media in HVAC systems from outdoor air.
著者関連情報
© 2012 日本建築学会
前の記事 次の記事
feedback
Top