特集—防災の観点からの燃焼挙動把握とその対策技術
高圧水素噴出火炎の特性と対策技術
武野 計二
著者情報
ジャーナル フリー

2010 年 52 巻 160 号 p. 121-129

詳細
抄録

The utilization of hydrogen for energy use is attractive since the exhaust gas is H2O alone and will spread widely, when renewable energies and CO2 reduction technologies are combined with the hydrogen-oxygen energy chain. In order to promote the widespread use of fuel cell vehicles, supply stations of high pressure hydrogen should be constructed in a city area, based on the safety regulations such as maximum storage amount, layout, material, safety distance, or protection wall. For the purpose, fundamental data for the open-jet hydrogen flame of high-pressurized hydrogen up to 80MPa have been accumulated. In this report, the scale of diffusion flame, flame stabilization, and radiation from flame are discussed. Furthermore, when the blown-down cloud of high pressure hydrogen was ignited at several tens milliseconds delay, the flame propagated at a high speed over 400m/s through the hydrogen-air mixture with a strong turbulence. Moreover, the outline of risk assessment and safety countermeasures for hydrogen supply station is introduced.