浅部地中熱利用に実装した場合の 5kW 級冷暖房用ブラインヒートポンプの熱性能
佐藤 貴志, 小熊 正人
著者情報
会議録・要旨集 フリー

詳細
抄録

Heat demand in the general housing, so is shown next generation energy conservation standards, it is predicted maximum heat demand from the relationship between outside air temperature and the set room temperature. In heat output 5kW about and think from this point of view, air-conditioning correspondence is possible heat pump is considered appropriate. For 5kW class of heating and cooling for the brine heat pump, to report the results of testing the brine return assumed thermal performance when the temperature is mounted on the high shallow geothermal heat from the ground. The test results, energy consumption efficiency is 2.7 to 4.4 in the heating test, became the 2.4 to 5.7 in the cooling test.