空気調和・衛生工学会大会 学術講演論文集
Online ISSN : 2424-2179
Print ISSN : 1880-3806
ISSN-L : 1880-3806
平成18年
セッションID: F-51
会議情報
F-51 病院施設における室内環境の衛生管理に関する研究 : (第1報)調査の概要と空気環境法定測定の結果
鍵 直樹池田 耕一柳 宇塩津 弥佳小畑 美知夫高柳 保斉藤 敬子鎌倉 良太吉野 博
著者情報
会議録・要旨集 フリー

詳細
抄録
It is important to maintain indoor air and sanitary environments in waiting lounges, office moms and medical wards of medical facilities. But Japan has no environmental and hygiene law for medical facilities. In this study, the way of the maintenance of sanitary environments in medical facilities was examined. This part reports the measurements of temperature, humidity, airflow rate, CO, CO_2, PM and formaldehyde concentrations in waiting lounges, office moms and medical wards of 9 medical facilities. As a result, humidity values in most part of the rooms were relatively low level. The CO_2 concentration in the waiting lounge that had a lot of out patients in that area was pretty high, therefore the capacity of the ventilating facilities might be exceeded.
著者関連情報
© 2006 公益社団法人 空気調和・衛生工学会
前の記事 次の記事
feedback
Top