F-52 病院施設における室内環境の衛生管理に関する研究 : (第2報)室内空気環境の連続測定結果
柳 宇池田 耕一鍵 直樹塩津 弥佳小畑 美知夫高柳 保斉藤 敬子鎌倉 良太吉野 博
著者情報
会議録・要旨集 フリー

詳細
抄録
The continuous measurements of indoor air quality and thermal environment, aimed at obtaining the way of maintenance of sanitary environment, in nine hospitals (A-I) were carried out from November 16 to December 22, 2005. Although the mass concentration of suspended particle, carbon monoxide and carbon dioxide concentration, air temperature, air velocity satisfied with environment management standard of "Law for Maintenance of Sanitary environment in Buildings ", almost all relative humidity was lower than the standard. Moreover, it became clear that the concentration of suspended particle larger than 2 micrometers in waiting rooms was greatly influenced by the number of visitors. Further studies on airborne microbe which is related to the particles larger than 2 micrometers are necessary.