F-53 病院施設における室内環境の衛生管理に関する研究 : (第3報)室内環境の衛生管理現状
池田 耕一柳 宇鍵 直樹塩津 弥佳小畑 美知夫高柳 保斉藤 敬子鎌倉 良太吉野 博
著者情報
会議録・要旨集 フリー

詳細
抄録
Investigations about the present conditions of maintenance of sanitary environment, such as an air conditioning system, plumbing system in 9 hospitals were conducted. The main results are shown as follows. (1) On the whole about maintenance of an air conditioning system, check of a cooling tower, humidification equipment, and an air-conditioner drainage receptacle and cleaning of a cooling tower, a cooling-water pipe, and humidification equipment are performed appropriately. On the other hand, measurement of indoor air environment was not conducted. (2) The maintenance situation of a water supply system was good compared with other equipment. (3) Since there is not any regulation of sanitary environment in medical facilities, maintenance of hot water supply systems, non-potable water supply equipment, drainage system, cleaning, and a rat noxious insect, were not performed appropriately.