浸透説による冷却塔の気・水各境膜値の推定
矢崎 嘉義岡 秀晃
著者情報
ジャーナル フリー

1995 年 12 巻 2 号 p. 211-217

詳細
抄録
In the experimental analysis of cooling towers, it is not necessarily easy to obtain the values of air and water phase film volumetric coefficients, because the experimental conditions are limited to which the Mickley's graphical method is applicable.
The purpose of this study is to predict the individual coefficients using more practical method based on the penetration theory for water film. The tower used in this study is of a commercial induced draft counterflow type. Water-cooling experiments were made with constantly designed air and water flow rates and with varied water temperatures. Then, we attempted to predict the individual coefficients from these over-all results by means of the reported procedure.
Finally, applying our method to the similar experimental date of other workers, we obtained nearly equal results compared with the Mickley's method.
著者関連情報
© 1995 公益社団法人 日本冷凍空調学会