1999 年 16 巻 2 号 p. 115-121
Duty cycling of centrifugal chillers has been considered an effective method for demand side management. Full scale experiments were performed to identify that unloading was a necessary step so that excessive mechanical wear would not occur due to cycling operation. On the other hand, reciprocating and screw compressors can adapt to cycling operation successfully.